VALSTEAM ADCA CDV32 COMPLIMENTARY EQUIPMENT
The CDV32 condensate drain valve automatically discharges air and condensate from steam systems during start-up. A compression spring keeps the valve open when the system is not pressurized. As soon as the operating pressure reaches the closing pressure to which the CDV is set, the valve closes. If the operating pressure drops below the closing set pressure, the spring force will cause the CDV32 to open once again.
MATERIAL
Carbon steel
SIZES
1/2” to 3/4”; DN 15 to DN 20
CONNECTIONS
Female threaded ISO 7 Rp or NPTFlanged EN 1092-1 PN 40Flanged ASME B16.5 Class 150 or 300Socket weld (SW) ASME B16.11Butt weld (BW) ASME B16.25 on request
MAX. OPERATING PRESSURE
22 bar
MAX. OPERATING TEMPERATURE
250 ºC
FLOW RATE CAPACITY
Up to 780 kg/h