VALSTEAM ADCA CDV32 COMPLIMENTARY EQUIPMENT

The CDV32 condensate drain valve automatically discharges air and condensate from steam systems during start-up. A compression spring keeps the valve open when the system is not pressurized. As soon as the operating pressure reaches the closing pressure to which the CDV is set, the valve closes. If the operating pressure drops below the closing set pressure, the spring force will cause the CDV32 to open once again.

MATERIAL

Carbon steel

SIZES

1/2” to 3/4”; DN 15 to DN 20

CONNECTIONS

Female threaded ISO 7 Rp or NPTFlanged EN 1092-1 PN 40Flanged ASME B16.5 Class 150 or 300Socket weld (SW) ASME B16.11Butt weld (BW) ASME B16.25 on request

MAX. OPERATING PRESSURE

22 bar

MAX. OPERATING TEMPERATURE

250 ºC

FLOW RATE CAPACITY

Up to 780 kg/h